TH/EN

07 / Fans & air distribution

Fans, ducts & air distribution

Useful airflow comes from a fan and a distribution system that fit.

A catalogue maximum may describe a low-resistance condition. Adding ducts, filters and terminals changes the airflow. Selection must pair the required flow with the pressure the actual system needs.

Supply, exhaust and circulation duties serve different purposes. Duct layout and terminal placement deserve the same attention as the fan itself.

Content reviewed 6 October 2026

Discuss the application →
Fans, ducts & air distribution
Centrifugal fan for moving air through ducts and filters.

Find the restriction before increasing fan size

Low delivery can result from loaded filters, closed dampers, undersized ducts, leakage or poor inlet/outlet conditions. High fan discharge flow still does not prove delivery to all zones.

Check model, speed, filter state, damper positions and branch flows before modification. More speed can add noise and input while leaving the distribution problem intact.

The duty point joins fan and system curves

A fan curve relates flow and pressure at a specified speed and test condition. A system curve describes the pressure required as flow changes. Their intersection is the operating point.[1]

For suitable fixed-path flow conditions, many resistance components can be approximated by Δp = KQ². Room-pressure offsets, moving dampers or different flow regimes need appropriate treatment. Use matching static/total-pressure and density bases.

Curves calculated from the stated illustrative equations. The same fan intersects two resistance curves at different duties. These are not tested product data.
Curves calculated from the stated illustrative equations. The same fan intersects two resistance curves at different duties. Open full-size illustration ↗

Choose type from duty, not appearance

Type/approachContextCheck
General axial fanHigh flow with low resistanceModel curve, sound and installation
Centrifugal fanDuct/filter resistance appropriate to the modelImpeller, input, duty point and stable range
Specialised axial or other designsEngineered pressure/performance dutiesDo not equate with common low-pressure axial products
Compatible EC/BLDC or variable-speed driveChanging flow or loadsMotor/drive compatibility and sequences; not a substitute for sizing

Impeller and motor arrangements vary. Pressure claims need model curves; no fan category wins every application.

Specify the complete duty

  • Required flow and path pressure: intake, filters, ducts, terminals and relevant room pressure.
  • Consistent pressure definition and air-density basis.
  • Stable range, efficiency, shaft/motor input and drive capability across the intended range.
  • Sound data with matching methods and distances.
  • Environment, material, mounting and access to the fan and motor.

Installation can change tested performance

Swirl or non-uniform inlet flow and unsuitable outlet transitions/bends can create system effect. Allow the layout to support the required air development and account for installed losses.[2]

There is no universal straight-duct distance in this illustration. Use guidance relevant to the fan and manufacturer. A rectangular fan discharge feeding round duct needs a real, properly designed connected transition.

Functional duct comparison: orderly entry and a complete transition versus disturbed flow close to the fan. No universal distance or loss percentage is specified.
Functional duct comparison: orderly entry and a complete transition versus disturbed flow close to the fan. No universal distance or loss percentage is specified. Open full-size illustration ↗

Application: filtered supply into a sealed room

Verify from the machine to the occupied zone

  • Model, speed, rotation, installation and filter/damper states.
  • Flow and pressure using suitable methods and locations, with pressure definition recorded.
  • Branch balancing and relevant occupied-zone velocities.
  • Speed commands, alarms and electrical input within the agreed scope.

Record a baseline to distinguish later loading, layout and demand changes. Rebalance when terminals or use change. A single sensor point needs justification before it represents the entire system.

Verification chain: fan identity/speed, system pressure, branch flow and occupied-zone distribution.
Verification chain: fan identity/speed, system pressure, branch flow and occupied-zone distribution. Open full-size illustration ↗

Siamphat selects the fan with the ducts and terminals

We connect air duty to path resistance, controls, sound, installation and verification. Equipment is assessed as part of the system it must serve.

Bring airflow plans, fan/filter details, weak-delivery locations and spatial constraints. Where drawings are absent, the operating brief guides what needs surveying.

Questions about fans and ducts

Can maximum catalogue flow select the fan?

Select at the actual required pressure; low-resistance maximum delivery can be very different.

Does filter loading always reduce flow?

Fixed-speed operation typically changes duty; flow-controlled systems may increase speed until a limit. Check the actual sequence.

How much energy does reducing speed save?

Similarity laws have conditions. System duty, efficiency and load determine actual input; do not infer a project percentage from speed alone.

How much straight duct is required?

Use fan-specific inlet/outlet and manufacturer guidance, not a universal distance.

References and scope

  1. AMCA — Straightening Out Fan Curves ↗
  2. AMCA — Mitigating System Effect to Optimize Fan Performance and Efficiency ↗
  3. ASHRAE Handbook — Air Handling and Distribution (2020) ↗

Sources support principles; they are not product certificates or a claim of project compliance. Actual design requires the applicable editions, requirements, model data and installation conditions. Residential or general sensor guidance does not substitute for special-purpose building criteria.

Connect the complete system

Read the related engineering article ↗

DISCUSS YOUR PROJECT

Strong fan, but insufficient useful airflow?

Discuss the fan, ducts, filters and terminals together with us to assess the operating point and airflow path.

Start with a plan, site photographs, existing equipment and the times when the problem occurs.